Home >> Products >> Electric energy saving-reactive
Electric energy saving-reactive
RVC-J/K Intelligent Reactive Power Compensation Controller
Model Number:   RVC-J/K
Authentication:   UL; CE; FCC; CMA; CNAS
Industrial Standard:   IEC; EU
Other:   PFC & PFP
    Product Information
Product introduction

This controller is designed for domestic market and has been widely used by electric power systems and switch cabinet manufacturers in Guangdong, Hunan, Guangxi and Jiangsu, etc. It has powerful functions, field LCD, reliable and stable performance and high interference resistance.

Product model number explanation

Programmable parameters

CT transformation ratio: 100-8000 (automatically adapting to the phase alternation on CT side of network)

COSφ target value: inductive: 0.70-1.00; capacitive: 0.70-1.00

C/K value: 0.01-0.99

Total harmonic distortion (THD): 0.05-0.40

Step delay: 1-120s

Max. output ways: 12

Undervoltage value: 300-380V

Overvoltage value: 420-460V

Sequence type: 1.1.1-1.2.8

Alarm switch: ON/OFF

Switching step delay: 1-240s

Delay between steps: 45s

Any step can be set normally ON or OFF

Voltage phase sequence: 0-330

Switching sequence type: 1:1:1~1:2:8 optional

Programmable early connection early disconnection or early connection late disconnection

RS 232/485 communication, MODBUS protocol output

Alarm and protection functions

Under current alarm and disconnecting step capacitor

Overcurrent alarm

Overvoltage alarm and disconnecting step capacitor

Undervoltage alarm

Low COSФ alarm (lower than COSФ set value when all connected)

Abnormal COSФ alarm

Capacitance lower than 70% alarm

Alarm at 60℃and disconnecting step capacitor at 70℃

THD higher than set value alarm and disconnecting step capacitor

Wrong frequency alarm

GE-PF 100V/120V series control schematic diagram

Basic specifications

Operating voltage: 260V~440V

Frequency range: 50Hz/60Hz ±5%

Input current: 0-5A

Output voltage: DC 12V or AC 90V~440V

Output ways: 12

Power consumption: <15W

Operating temperature: -25℃~+70℃

Relative humidity: max. 95% without condensation

Weight: 1.00kg (excluding package)

Elevation: ≤3500M

Overall dimensions: 144mm×144mm×80mm (L × W × D)

Opening dimensions: 138mm×138mm (L × W)

Standards for GE-PF 100V/120V series products
GB/T14549-199 Power System Harmonic Management Standard

GB/T15576-1995 The specification of low-voltage reactive power steady compensation equipment

JB/T9663-1999 Low voltage reactive power automatic compensating controller

DL/T597-1996 Low voltage reactive power compensation controller ordering specifications

Products meet UL and CE certification standards and EMC standards of EU for operation at 50/60HZ

COPYRIGHT   深圳市华润通科技有限公司版权所有   2001-2011   地址:深圳市罗湖区宝安南路3083号蔡屋围发展大厦1803

TEL:0755-82127848 / 82128238 / 33393678      Fax: 0755-82127849     E-mail:hrt@hrttech.com     网址:www.hrttech.com